An investigation in the voltage response and fault handling capabilities of an induction generator wind turbine on an A1 distribution network

Wiktora, Michael (2011) An investigation in the voltage response and fault handling capabilities of an induction generator wind turbine on an A1 distribution network. Internship Report, Murdoch University.

[img]
Preview
PDF - Front Pages
Download (563kB) | Preview
    [img]
    Preview
    PDF - Whole Thesis
    Download (1545kB) | Preview

      Abstract

      With projected increases in green energy production, the integration of these new technologies is becoming an increasing cause for concern. As such, this thesis aims to investigate the integration of a particular wind turbine technology, or configuration, on a specific section of the local South West grid (SWIS). This thesis will focus on steady state voltage stability, transient post fault generator response, and voltage decline due to the starting of the generators. It will also compare the transient findings of this turbine configuration to that of another turbine configuration.

      The wind farm that is simulated will be called the type A Wind Farm, and consists of 12 Vestas V82 type A turbines. They are active stall controlled units, which connect the turbine rotor blade to the induction generator rotor via a gearbox. These are coupled with soft starters and are provided with reactive power compensation in the form of switchable capacitor banks. A step up transformer brings the generation voltage up to distribution level, which in this case is 22kV.

      The A1 distribution network is a specific section of grid upon which all power flow calculations take place. This is an arbitrary name given to an actual section of network due to confidentiality reasons. It has been used as it lies on the extremities of the SWIS, and will best indicate how such a wind turbine generator will impact a weaker section of grid. It is also the same network used by Fidock (2010), for his studies on a type D turbine configuration, and as such will provide a good baseline for comparisons between the two technologies.

      The findings of this thesis indicate that steady state operation of the type A turbine configuration produces voltages within acceptable limits. Starting of these generators can also be handled by this section of the network, however soft starters are recommended and smart operator control is essential. Due to their high reactive power draw following a network fault, it is highly recommended that turbine configurations of this construct be disconnected from the grid post fault, and reconnected after the grid has stabilized. A comparison of the two different technologies indicates that type A has much less voltage and power flow control compared to type D. The results also indicate that widespread integration of type A wind turbine generators be extremely limited, and large wind farms of this technology should not be installed on the extremities of the grid.